Underground Wiring Requirements

It’s not uncommon to want to run 120V wiring underground. You may want to send power to your shed or garage, or you may be interested in wiring up a lamp post or electric gate motor. In either case, there are a few details you’ll need to be aware of in order to meet current building codes.

Southwire SIMPush Push-to-Install Conduit Fittings for EMT

It’s not uncommon to want to run 120V wiring underground. You may want to send power to your shed or garage, or you may be interested in wiring up a lamp post or electric gate motor. In either case, there are a few underground wiring requirements you’ll need to be aware of in order to meet current building codes.



Underground Wiring Requirements – The Basics

First off, it’s not necessary to run the wiring in conduit if you follow a few basic rules:

  • You must bury the wire a minimum of 12-inches below the ground (with GFCI) or 18-inches (without GFCI)
  • If you decide on direct-burial, you must use a PVC-jacketed Type UF (underground feeder) cable.
  • You must place a GFCI on the circuit
  • You must keep the maximum overcurrent protection of the circuit to 20 amps (20A breaker)

If you want to use metal conduit, you can. Typically this will be gray PVC and can be 3/4-inch diameter for a single line. Check with your local building codes to verify whether or not you can use PVC, as metal conduit may be specified. In addition, the required burial depths may be different for each. If you use conduit, it can be sealed and you can use regular 12/2 wiring instead of direct-burial cable.

Know Your Local and State Codes

The main thing for understanding underground wiring requirements is to double-check your local codes, but realize your options and take the safest or simplest route depending on your situation. If you can get away without conduit and the wiring is in an area that isn’t liable to get in the way of future digging, then direct-burial cable might be best. If you’re running through the middle of your yard, then a PVC or metal conduit might be a great idea, regardless if it’s required to meet code.

Nothing’s better than getting much-needed power to a shed or garage, so attack this type of project with gusto and reap the benefits. As always, consult or use a licensed electrician if things seem to be beyond your level of expertise.

Related articles

How to Cut Soil Pipe – Pro Plumbing Tips

Cutting in-place soil pipes might be an unpleasant job but it doesn’t have to be difficult. All of these methods work, other things being equal, but soil pipe access might eliminate some of them. The age and condition of the pipe might affect the method you use for cutting it as well (it gets even more […]

The Tool Fool’s Stool – The Great Tool Review Coverup

There comes a time in every man’s life when they must stand up for themselves. For too long my voice has been suppressed on this site. You may be asking yourself, “Who is this guy?” Exactly. When this “site” was a real publication—i.e. a PRINT MAGAZINE, I had the last word on each issue. That’s […]

Types of Wood Drilling Bits – Use the Right One

Most of us are guilty of using the wrong tool for the job—either out of necessity or laziness. Still, there’s something satisfying about using the right tool for the job. Often, using the right tool helps bring about the best possible result. When drilling, accessories matter—possibly even more than the tool you choose. Knowing the […]

Subscribe
Notify of
guest
0 Comments
Inline Feedbacks
View all comments
0
Would love your thoughts, please comment.x
()
x